Siemens SENTRON 3VA1120-4ED12-0AA0, molded case circuit breaker, 1-pole, 20 A rated at 40 °C, TM210 overcurrent release, 75.6 kA interrupting capacity at 240 V AC, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-4ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1120-4ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Rated insulation voltage Ui500 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classS
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V9 kA
Power loss, max.4 W

Protection & Trip Unit

3VA1120-4ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1120-4ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-4ED12-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1120-4ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-4ED12-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1120-4ED12-0AA0 is a 1-pole molded case circuit breaker (MCCB) rated 20 A at 40 °C with a TM210 thermal-magnetic overcurrent release. It delivers a 75.6 kA interrupting capacity at 240 V AC and 9 kA at 415 V AC, sized for line protection in distribution panels. The 20 A rating holds flat from 40 °C through 55 °C, then derates to 19 A at 60 °C and above — no need to oversize for typical 40 °C panel ambient. Insulation voltage is 500 V, with operating voltage at 415 V AC or 125 V DC.

Integration & Mounting

The 25.4 mm (1 in) width and 70 mm (2.76 in) depth fit standard 1-pole MCCB slots in Siemens SENTRON distribution panels. Front IP40 protection covers the operator interface; the TM210 release is fixed, no trip indicator or undervoltage release on this variant.

Frequently asked questions

What is the interrupting capacity of 3VA1120-4ED12-0AA0?

75.6 kA at 240 V AC and 9 kA at 415 V AC — sufficient for high-fault panelboard applications.

Where can I buy 3VA1120-4ED12-0AA0?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

MPN