Skip to main content
Siemens 3VA1120-4EF32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-4EF32-0AE0 SENTRON MCCB, 3-pole, 20 A, 121 k

MPN3VA1120-4EF32-0AE0

Siemens SENTRON 3VA1120-4EF32-0AE0, molded case circuit breaker, 3-pole, 20 A rated current, 121 kA interrupting capacity at 240 VAC, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1120-4EF32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11204EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1120-4EF32-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.12 W
3VA1120-4EF32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1120-4EF32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1120-4EF32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1120-4EF32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1120-4EF32-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1120-4EF32-0AE0 — SENTRON MCCB, Line Protection, 20 A

The Siemens SENTRON 3VA1120-4EF32-0AE0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, rated at 20 A continuous current at 40 °C and carrying a 121 kA interrupting capacity at 240 VAC — enough to handle high-fault utility feeds without cascading upstream. Rated insulation voltage is 800 V, and the interrupting curve holds at 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V, so it covers 480Y/277 V and 600 V industrial services with headroom. The TM240 thermal-magnetic overcurrent release is fixed-trip, non-adjustable — set it and forget it for dedicated motor or feeder circuits where coordination studies have already locked the pickup.

At 76.2 mm wide, 130 mm tall, and 70 mm deep, this 3-pole MCCB fits standard Siemens 3VA panel footprints and mounts via the rear screw-clamp or optional DIN-rail adapter — verify gland-plate clearance for the 70 mm depth when the breaker sits behind a deadfront. Power loss is 12 W maximum at rated load, so the enclosure thermal rise stays manageable in a grouped panel; no forced ventilation required unless the ambient exceeds 40 °C.

Auxiliary Switching and Accessories

Add those as separate accessories if the spec requires remote trip or GFCI. The trip indicator is absent on this version — visual flag is not provided; if panel walk-by inspection needs a clear tripped/on state, specify the variant with the mechanical flag.

Frequently asked questions

Does 3VA1120-4EF32-0AE0 include auxiliary contacts?

Yes, it ships with a factory-fitted HQ auxiliary switch block providing 4 auxiliary contacts for status feedback.

MPN
3VA1120-4EF32-0AE0