Skip to main content
Siemens 3VA1120-4EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-4EF32-0CA0 SENTRON MCCB, 20 A, 3-Pole, 121 k

MPN3VA1120-4EF32-0CA0

Siemens SENTRON 3VA1120-4EF32-0CA0, molded case circuit breaker, 3-pole, line protection, 20 A rated, 121 kA at 240 V, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1120-4EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1120-4EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1120-4EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1120-4EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1120-4EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1120-4EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1120-4EF32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity hits 121 kA at 240 V, 75.6 kA at 415 V, and 52.5 kA at 440 V; at 690 V it still manages 11.9 kA. That spread means it can sit at the main or branch in a 480 V panel and still interrupt a serious fault without the arc flash climbing upstream.

At 55 °C it derates to 19.2 A, at 60 °C to 18.8 A, at 65 °C to 18.4 A, and at 70 °C to 18 A. The front face is IP40, so it's fine inside a closed panel; no washdown rating, so keep it out of wet zones.

Width is 76.2 mm (roughly 3 inches), depth 70 mm, height 130 mm. That footprint matches the standard SENTRON 3VA platform — if the panel was laid out for a 3VA11 frame, this drops in on the same mounting holes and bus connections.

Lifecycle stage is current — Siemens still builds this exact variant. No phase-out notice, no last-time-buy. For a BOM line that needs an active MCCB with a known interrupting rating at multiple voltages, this part is a straight spec-in.

Frequently asked questions

Where can I buy 3VA1120-4EF32-0CA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ to get a firm price and lead time.

Will 3VA1120-4EF32-0CA0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are SENTRON 3VA frame breakers with the same 76.2 mm width, 70 mm depth, and 130 mm height, so the mechanical footprint is identical. The 3VA1112-5EF32-0CA0 carries a higher 125 A rating, so the bus and lug sizing must match the downstream load — the breaker itself will bolt in, but verify the conductor ampacity and the upstream protective device coordination before swapping.

What compliance documentation does Siemens provide for 3VA1120-4EF32-0CA0?

Siemens typically supplies a CE declaration of conformity and a UKCA declaration for the SENTRON 3VA series. RoHS and REACH compliance are standard for current-production Siemens MCCBs. Specific certificates (UL, IEC) are available on request from the manufacturer or through the distributor at quote time.

MPN
3VA1120-4EF32-0CA0