Skip to main content
Siemens 3VA1120-5ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-5ED22-0AA0 SENTRON MCCB, 20 A, 2-pole, 187 k

MPN3VA1120-5ED22-0AA0
Active

Siemens SENTRON 3VA1120-5ED22-0AA0, molded case circuit breaker, 2-pole, 20 A rated continuous current, interrupting capacity 187 kA at 240 V AC, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-5ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1120-5ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Power loss, max.8 W

Protection & Trip Unit

3VA1120-5ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1120-5ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-5ED22-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1120-5ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-5ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.1 in
Width (in)2 in
Depth (in)2.8 in

Product details

Key ratings and what they mean for fit

The Siemens 3VA1120-5ED22-0AA0 is a SENTRON molded case circuit breaker (MCCB) in the line protection version, rated for a continuous current Iu of 20 A across the ambient range from 40 °C to 55 °C — it holds 20 A flat through that band, then derates to 19 A at 60 °C through 70 °C. That thermal stability means the breaker doesn't force a cable upsize just because the panel runs warm; the trip curve stays consistent within the normal enclosure temperature envelope. The interrupting capacity is the headline number here: 187 kA at 240 V AC and 121 kA at 415 V AC. Those are high-rupturing-capacity figures for a 20 A frame — this breaker can sit at the service entrance or on a high-fault panel where the available short-circuit current is substantial, without needing a current-limiting fuse upstream. The 2-pole configuration suits single-phase or two-leg line protection.

Mounting and panel integration

The breaker measures 70 mm deep by 50.8 mm wide by 130 mm high — a 2-inch-wide footprint. The front face carries an IP40 protection rating.

Adjustable trip settings and release design

The overcurrent release is a TM210 — thermal-magnetic, fixed thermal and magnetic adjustment. The Ir is fixed at 20 A. The instantaneous magnetic pickup Ii is set at 320 A.

Electrical ratings and approvals context

Rated insulation voltage Ui is 500 V AC; maximum DC operational voltage is 250 V. The power loss at rated current is 8 W maximum. Storage temperature range is -40 °C to 80 °C; operating ambient is -25 °C to 70 °C.

Frequently asked questions

What is the depth of 3VA1120-5ED22-0AA0?

The depth is 70 mm (2.8 inches). Combined with a width of 50.8 mm and height of 130 mm, it fits standard MCCB panel cutouts and DIN-rail adapter plates.

MPN
3VA1120-5ED22-0AA0