SENTRON 3VA1120-5EF32-0AH0 — 20 A MCCB with TM240 release
Three-pole construction with a TM240 thermal-magnetic release. The interrupting ratings drop as system voltage rises: 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V — the 17 kA floor at 690 V still covers most industrial motor-control center fault levels.
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or direct-mount panel layouts. The auxiliary contacts share the same mounting space — no extra DIN rail needed. Maximum power loss is 12 W at rated current. That is low enough to avoid forced ventilation in a standard IP54 enclosure, but check the cumulative heat if you pack multiple breakers in a small cabinet.