Its breaking capacity reaches 187 kA at 240 VAC, 121 kA at 415 V, and 75.6 kA at 440 V — figures that govern fault-clearing ability at the point of common coupling.
Current rating holds at 20 A from 40 °C through 55 °C, then derates to 19 A at 60 °C through 70 °C — a flat thermal curve that simplifies panel sizing in warm enclosures. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON 3VA mounting footprint for panel or enclosure integration.