Siemens 3VA1120-6ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-6ED36-0AA0 SENTRON MCCB, 20 A, 3-Pole, 220 k

MPN3VA1120-6ED36-0AA0
Active

Siemens SENTRON 3VA1120-6ED36-0AA0, molded case circuit breaker, 3-pole, 20 A rated current, TM210 overcurrent release, 220 kA breaking capacity at 240 V AC, line protection design, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-6ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1120-6ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1120-6ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1120-6ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-6ED36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1120-6ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-6ED36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1120-6ED36-0AA0 — 20 A MCCB for Line Protection

The Siemens 3VA1120-6ED36-0AA0 is a SENTRON-series molded case circuit breaker (MCCB) rated for 20 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release and three poles for three-phase line protection. Its 220 kA interrupting capacity at 240 V AC means it can safely clear a bolted fault on a high-capacity transformer secondary without the arc flashing over to adjacent gear — a critical parameter for panel builders sizing the SCCR of a distribution board.

Ratings and What They Mean for Your Panel

Rated current holds at 20 A from 40 °C through 55 °C ambient, derating only to 19 A at 60–70 °C — so in a warm enclosure the breaker still carries its full nameplate load up to 55 °C. The TM210 release is a fixed thermal-magnetic type, meaning no interchangeable trip units; the breaker itself is the calibrated element. Breaking capacity drops from 220 kA at 240 V to 154 kA at 415 V, then 121 kA at 440 V, and 17 kA at 500 V and 690 V — the steep drop above 480 V means this is primarily a 240 V / 480 V class device; for 690 V applications the available fault current must be verified against the 17 kA rating.

Physical Fit and Panel Integration

The breaker measures 76.2 mm wide (3 in), 130 mm tall (5.12 in), and 70 mm deep (2.76 in) — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures with the appropriate SENTRON mounting accessories. Front IP40 protection means it is suitable for general-purpose indoor panels but not washdown areas. No undervoltage release or shunt trip is fitted as standard; those are add-on accessories if the safety circuit requires a remote trip.

Approvals and Compliance Documentation

As a Siemens SENTRON product, this MCCB carries CE marking for the European market and is designed to meet IEC 60947-2. UL and CSA listings are typical for the 3VA family, though specific certification details should be confirmed from the nameplate or factory certificate. RoHS and REACH compliance documentation is available from Siemens per standard industrial practice.

Frequently asked questions

What is the breaking capacity of 3VA1120-6ED36-0AA0 at different voltages?

At 240 V the interrupting rating is 220 kA; at 415 V it is 154 kA; at 440 V it is 121 kA; and at 500 V and 690 V it drops to 17 kA. The steep decline above 480 V means this breaker is best applied on 240 V or 480 V systems where high fault current is expected.

Where can I buy 3VA1120-6ED36-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm price and lead time.

MPN