Siemens 3VA1120-6EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1120-6EE32-0AA0 MCCB, 20 A, 3-Pole, TM220

MPN3VA1120-6EE32-0AA0
Active

Siemens SENTRON 3VA molded case circuit breaker, 3VA1120-6EE32-0AA0, 3-pole, 20 A, TM220 thermal-magnetic release, line protection, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-6EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1120-6EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1120-6EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1120-6EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-6EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1120-6EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-6EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1120-6EE32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 20 A continuous current across a 40 °C to 55 °C ambient range, derating to 19 A at 60 °C and above. It uses a TM220 thermal-magnetic overcurrent release — the fixed thermal element handles overloads, the magnetic trip handles short-circuits — and is designed for line protection in distribution panels.

Mounts on a DIN rail or panel-mount base. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard 3-pole MCCB cutouts. Front face carries IP40 protection; the enclosure is not rated for washdown environments.

The breaking capacity is the headline number for this class: 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. That 220 kA figure at 240 V means it can safely interrupt a fault current up to that level without venting or cascading to upstream breakers — critical for high-fault installations like transformer secondaries or large motor control centers. The 800 V rated insulation voltage (Ui) confirms it's suitable for 480 V and 600 V class systems with margin.

Power loss at rated current is 12 W maximum. Operating temperature range is -25 °C to +70 °C; storage from -40 °C to +80 °C. No undervoltage release, no ground-fault monitoring, no communication function on this variant — it's a straight thermal-magnetic breaker for line protection.

Frequently asked questions

How do I get current pricing and availability for 3VA1120-6EE32-0AA0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels.

What is the breaking capacity of 3VA1120-6EE32-0AA0 at 240 V?

220 kA at 240 V AC, making it suitable for high-fault-current applications like transformer secondaries.

Will 3VA1120-6EE32-0AA0 drop into a panel specified around 3VA1110-5ED32-0AA0?

Both are 3-pole SENTRON 3VA breakers with the same 70 mm depth and 76.2 mm width, so the footprint is identical. The key difference is the overcurrent release: 3VA1120-6EE32-0AA0 uses a TM220 (20 A fixed thermal-magnetic), while 3VA1110-5ED32-0AA0 uses a different release. Verify the trip curve and amp rating match your branch circuit before swapping.

MPN
3VA1120-6EE32-0AA0