Skip to main content
Siemens 3VA1120-6EF32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1120-6EF32-0KH0 MCCB, 20 A, 220 kA at 240

MPN3VA1120-6EF32-0KH0

Siemens SENTRON 3VA1120-6EF32-0KH0, 3-pole molded case circuit breaker, 20 A rated at 40 °C, 220 kA interrupting at 240 V, line protection with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-6EF32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11206EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1120-6EF32-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1120-6EF32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1120-6EF32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-6EF32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1120-6EF32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-6EF32-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Rating and fit for line protection

The Siemens SENTRON 3VA1120-6EF32-0KH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 20 A continuously at 40 °C ambient — a rating that holds steady through 55 °C before derating to 19 A at 60 °C. Its interrupting capacity reaches 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V, with a floor of 17 kA at 500 V and 690 V. That 220 kA figure at 240 V means it safely clears high-fault currents in low-voltage distribution without cascading upstream — a critical parameter for panel coordination studies. The rated insulation voltage of 800 V gives headroom for 480 V and 600 V class systems.

Integrated auxiliaries and release options

This MCCB ships with a factory-fitted shunt trip (STL) release and a complement of 2 auxiliary switches plus 1 trip alarm switch HQ. The shunt trip allows remote tripping via a control voltage — useful for emergency-stop circuits or supervisory shutdown sequences. The auxiliary switch set provides status feedback for PLC or SCADA monitoring. There is no undervoltage release fitted, no ground-fault monitoring module, and no communication function onboard — this is a straightforward line-protection device with wired auxiliaries, not a networked power breaker.

Panel fit and thermal management

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth — a compact 3-pole MCCB footprint that fits standard panel mounting. Maximum power loss is 12 W, which should be factored into enclosure thermal calculations, especially when multiple breakers are ganged. Operating temperature range is -25 °C to 70 °C; storage range extends from -40 °C to 80 °C. The trip indicator provides local visual status for troubleshooting without opening the panel door.

Lifecycle and compliance posture

The lifecycle stage is recorded as current production. This is an active Siemens SENTRON 3VA series part, not subject to phase-out notices at this time. For compliance documentation — RoHS, REACH, UL, IEC — the SENTRON family carries full declarations of conformity; the specific certificates are available on request as part of the supplier-quality package. This part is quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Frequently asked questions

Where can I buy 3VA1120-6EF32-0KH0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here, but a formal quotation will include both.

What compliance documentation is available for 3VA1120-6EF32-0KH0?

The SENTRON 3VA series carries full declarations of conformity for RoHS, REACH, UL, and IEC standards. Specific certificates are available on request as part of the supplier-quality documentation package.

What are the key ratings of 3VA1120-6EF32-0KH0?

It is a 3-pole MCCB rated 20 A continuous at 40 °C, with interrupting capacity of 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V. Rated insulation voltage is 800 V. It includes a shunt trip release and 2 auxiliary switches plus 1 trip alarm switch.

MPN
3VA1120-6EF32-0KH0