Skip to main content
Siemens 3VA1120-6EF36-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-6EF36-0AC0 SENTRON MCCB, 20 A, 3-Pole, 220 k

MPN3VA1120-6EF36-0AC0

Siemens SENTRON 3VA1120-6EF36-0AC0, molded case circuit breaker, 3-pole, 20 A rated at 40 °C, TM240 thermal-magnetic release, 220 kA breaking capacity at 240 VAC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-6EF36-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11206EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1120-6EF36-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1120-6EF36-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1120-6EF36-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-6EF36-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1120-6EF36-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-6EF36-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1120-6EF36-0AC0 — line-protection MCCB, 20 A frame

The Siemens SENTRON 3VA1120-6EF36-0AC0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection, carrying a 20 A rating at 40 °C ambient and a TM240 thermal-magnetic overcurrent release. It breaks up to 220 kA at 240 VAC, 154 kA at 415 VAC, 121 kA at 440 VAC, and 17 kA at both 500 VAC and 690 VAC — so the interrupting capacity drops sharply above 440 V; at 690 V the 17 kA figure governs the fault-current limit for that installation. The 800 V rated insulation voltage (Ui) means the breaker is rated for 690 V line-to-line systems without derating the internal isolation. This is a current-production part (lifecycle stage: current), so it moves through the standard Siemens distribution channel. No communication module, no ground-fault monitoring, no undervoltage release on this variant — it is a straight thermal-magnetic line-protection breaker with two HQ auxiliary switches built in.

Mounting and panel fit

The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. The 70 mm depth means it clears a typical 100 mm deep gland plate with room for wiring. Maximum power loss is 12 W, so in a sealed enclosure with multiple breakers side by side, account for that heat when sizing the cabinet ventilation.

Thermal derating and operating range

The breaker holds its 20 A rating from 40 °C through 55 °C; at 60 °C and 65 °C it derates to 19 A, and at 70 °C it stays at 19 A. Operating ambient range is -25 °C to +70 °C, storage from -40 °C to +80 °C. The trip indicator is absent on this variant — you will not get a visual flag; the auxiliary switches are the only remote status.

Frequently asked questions

What is the breaking capacity of 3VA1120-6EF36-0AC0 at different voltages?

At 240 V it breaks 220 kA; at 415 V, 154 kA; at 440 V, 121 kA; at 500 V and 690 V, 17 kA. The sharp drop above 440 V means the available fault current at the installation point must be verified against the 17 kA limit for 480/600 V class systems.

Where can I buy 3VA1120-6EF36-0AC0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What are the physical dimensions of 3VA1120-6EF36-0AC0?

Width 76.2 mm, height 130 mm, depth 70 mm — a standard 3-pole MCCB footprint.

Does 3VA1120-6EF36-0AC0 include a trip indicator or undervoltage release?

No. This variant has no trip indicator, no undervoltage release, no ground-fault monitoring, and no communication function. It carries two HQ auxiliary switches for remote status.

MPN
3VA1120-6EF36-0AC0