Skip to main content
Siemens 3VA1120-6EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-6EF36-0JA0 SENTRON MCCB, 20 A, 3-Pole, 220 k

MPN3VA1120-6EF36-0JA0

Siemens SENTRON 3VA1120-6EF36-0JA0, molded case circuit breaker, 3-pole, 20 A rated continuous current, 220 kA interrupting capacity at 240 V, line protection version with shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1120-6EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1120-6EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C19.2 A
Current at 60 °C18.8 A
Current at 65 °C18.4 A
Current at 70 °C18 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1120-6EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1120-6EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1120-6EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1120-6EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1120-6EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

MCCB for high-fault panel applications

It's built to handle serious fault current: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you this breaker is meant for high-available-fault-current panels where a standard MCCB would weld its contacts shut.

Above that it derates linearly: 19.2 A at 55 °C, 18.8 A at 60 °C, 18.4 A at 65 °C, and 18 A at 70 °C. The case dimensions are 130 mm high by 76.2 mm wide by 70 mm deep, and it carries an IP40 front protection rating, so it's fine for general indoor panel mounting but not for washdown areas. No auxiliary contacts, no communication module, no undervoltage release — this is a bare-bones line-protection breaker with a shunt trip for remote opening.

Frequently asked questions

Where can I buy 3VA1120-6EF36-0JA0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Current availability and pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1120-6EF36-0JA0 at various voltages?

It interrupts 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. These are the rated breaking capacities — match them to your system's available fault current.

Does 3VA1120-6EF36-0JA0 have a shunt trip?

Yes, it includes a built-in shunt trip (STL) for remote opening. The integrated auxiliary trip order code is 3VA9688-0BL32.

What is the thermal derating of 3VA1120-6EF36-0JA0 at elevated temperatures?

It carries 20 A up to 50 °C. Above that: 19.2 A at 55 °C, 18.8 A at 60 °C, 18.4 A at 65 °C, and 18 A at 70 °C. Derate accordingly if your panel ambient runs hot.

MPN
3VA1120-6EF36-0JA0