Skip to main content
Siemens 3VA1120-6GD46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1120-6GD46-0AA0 SENTRON MCCB, 20A, 4-Pole, 220kA

MPN3VA1120-6GD46-0AA0
Active

Siemens SENTRON, Molded case circuit breaker, 3VA1120-6GD46-0AA0, 4-pole, 20 A, TM210 release, 220 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1120-6GD46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1120-6GD46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.12 W

Protection & Trip Unit

3VA1120-6GD46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1120-6GD46-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1120-6GD46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1120-6GD46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1120-6GD46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

SENTRON 3VA1120-6GD46-0AA0 — 20 A 4-Pole MCCB with TM210 Release

The Siemens SENTRON 3VA1120-6GD46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated at 20 A continuous current, built around the TM210 thermal-magnetic release for line protection in distribution panels and motor branch circuits. Its interrupting capacity reaches 220 kA at 240 V AC, 154 kA at 415 V, and 121 kA at 440 V — figures that cover most industrial fault-current scenarios downstream of a transformer or generator main. At 690 V the rating drops to 17 kA, and the same 17 kA applies at 500 V, so for 690 V applications verify the available fault current stays within that ceiling. The TM210 release has an adjustable short-circuit pickup up to 320 A (li max), giving flexibility to coordinate with downstream breakers or motor starters without changing the breaker frame.

Thermal Performance and Derating

The 3VA1120-6GD46-0AA0 carries its full 20 A rating from 45 °C through 55 °C ambient without derating — a solid margin for typical panel environments. Above 55 °C, the current rating steps down to 19 A at 60 °C, 65 °C, and 70 °C, so a panel running near its upper thermal limit loses only 1 A of headroom. Maximum power loss is 12 W at rated load — modest enough that forced ventilation is rarely needed in a standard enclosure.

Integration and Mounting

The breaker occupies a 101.6 mm wide, 130 mm tall, 70 mm deep footprint — standard for a 4-pole SENTRON 3VA frame — and mounts directly onto a DIN rail or panel-mount adapter. Front-face protection is IP40, suitable for enclosed distribution boards; the N-conductor is protected at 100 % rating, meaning the neutral pole is fully rated rather than switched-only. An optional motor drive accessory (Product Extension / Optional / Motor Drive: Yes) allows remote motorized operation for automated or inaccessible panels.

Electrical Ratings and Compliance

Rated insulation voltage is 800 V AC; maximum operational voltage on DC circuits is 600 V, so the breaker can serve DC bus or battery-bank applications within that limit. Operating ambient range spans -25 °C to +70 °C, with storage from -40 °C to +80 °C — the storage ceiling matters for warehouses or unheated staging areas. No communication function is built in; this is a standalone line-protection breaker, not a metering or trip-unit-communicating variant.

Frequently asked questions

Does 3VA1120-6GD46-0AA0 support DC operation?

Yes, the maximum rated operational voltage on DC circuits is 600 V.

What type of release does 3VA1120-6GD46-0AA0 use?

It uses a TM210 thermal-magnetic release with an adjustable short-circuit pickup up to 320 A.

MPN
3VA1120-6GD46-0AA0