Rated 25 A continuous at 40 °C, it holds that rating through 50 °C and derates to 23 A at 70 °C — a thermal curve that suits panel environments where ambient heat builds near the top of the enclosure. Interrupting capacity is 52.5 kA at 240 V AC and 7.5 kA at 415 V AC — the 240 V figure covers common North American panelboard fault levels, while the 415 V rating handles European 400 V distribution. The 1-pole body is 25.4 mm wide, fitting a single module on a DIN rail; depth is 70 mm, height 130 mm.

Siemens 3VA1125-3ED12-0AA0 SENTRON MCCB, 25 A, 1-Pole, 52.5
MPN3VA1125-3ED12-0AA0
Active
Siemens SENTRON 3VA1125-3ED12-0AA0, molded case circuit breaker, 1-pole, 25 A (40 °C), interrupting rating 52.5 kA at 240 V AC, TM210 trip unit, IP40 front, 70 mm depth.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 1 |
| Rated operational voltage Ue (AC) | 415 V |
| Rated insulation voltage Ui | 500 V |
| Current at 40 °C | 25 A |
| Current at 45 °C | 25 A |
| Current at 50 °C | 25 A |
| Current at 55 °C | 24 A |
| Current at 60 °C | 24 A |
| Current at 65 °C | 23 A |
| Current at 70 °C | 23 A |
| Switching capacity class | N |
| Breaking capacity at 240 V | 52.5 kA |
| Breaking capacity at 415 V | 7.5 kA |
| Power loss, max. | 2.83 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 25.4 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 1 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
What are the key ratings for this MCCB?
Rated 25 A continuous at 40 °C, interrupting 52.5 kA at 240 V AC and 7.5 kA at 415 V AC. The TM210 trip unit provides thermal-magnetic overcurrent protection. It is a 1-pole device with a width of 25.4 mm.
Where can I buy 3VA1125-3ED12-0AA0?
This part is available to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.
MPN
3VA1125-3ED12-0AA0