The 3VA1125-3EE46-0AA0 is a 4-pole molded case circuit breaker from the Siemens SENTRON 3VA series, designed for line protection. It carries a continuous current rating of 25 A at ambient temperatures up to 50 °C, derating to 23 A at 70 °C — the full thermal curve is documented in the spec table.
Interrupting capacity by system voltage
Interrupting capacity varies with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Dimensions are 130 mm height, 101.6 mm width, 70 mm depth — a standard 4-pole MCCB footprint for DIN-rail or screw-mount panel installation. Rated insulation voltage is 800 V, and maximum power loss at rated current is 8.5 W, which should be factored into enclosure thermal calculations.