Skip to main content
Siemens 3VA1125-3EF32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-3EF32-0AF0 SENTRON MCCB, 25A, 75.6kA at 240V

MPN3VA1125-3EF32-0AF0

Siemens SENTRON 3VA1125-3EF32-0AF0, 3-pole molded case circuit breaker, 25 A rated at 40 °C, 75.6 kA breaking capacity at 240 V, TM240 thermal-magnetic release, line protection, HQ auxiliary switch + trip alarm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1125-3EF32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11253EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1125-3EF32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.8.5 W
3VA1125-3EF32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1125-3EF32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1125-3EF32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1125-3EF32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1125-3EF32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens 3VA1125-3EF32-0AF0 is a SENTRON molded case circuit breaker (MCCB) for line protection — the main disconnect and fault interruption in a distribution panel or motor control center. Three poles, rated 25 A continuous at 40 °C ambient, with a TM240 thermal-magnetic overcurrent release that handles both overload and short-circuit trips without external control power. Breaking capacity of 75.6 kA at 240 V AC means it can safely interrupt a fault current up to that level — enough for high-available-fault service entrances or industrial switchgear without cascading upstream breakers. Rated insulation voltage of 800 V. Power loss is 8.5 W maximum.

Auxiliary switching and monitoring

Factory-fitted with one auxiliary switch and one trip alarm switch (HQ configuration) — the trip alarm signals when the breaker has opened on a fault, separate from the manual ON/OFF position. Trip indicator visible on the front. No undervoltage release, no ground-fault monitoring, no communication module on this variant — it is a straight thermal-magnetic line protection breaker.

Dimensions and panel fit

Width 76.2 mm (3 in), height 130 mm (5.12 in), depth 70 mm (2.76 in). Standard 3-pole MCCB footprint for DIN-rail or panel-mount installation in a distribution board.

Frequently asked questions

Does this breaker include auxiliary contacts or a shunt trip?

It comes with one auxiliary switch and one trip alarm switch (HQ). It does not include an undervoltage release, shunt trip, or communication module — those are separate accessories on the 3VA platform.

MPN
3VA1125-3EF32-0AF0