The 25 A rating holds flat from 40 °C to 50 °C, then derates to 24 A at 55 °C and 23 A at 70 °C — so in a warm panel you lose only 1–2 A, not a full step. The 75.6 kA at 240 V is the headline interrupting rating; at 415 V it still breaks 52.5 kA, and at 690 V it holds 11.9 kA. That means it handles most industrial fault levels without needing a current-limiting upstream breaker.
Panel integration
The 3-pole form factor matches typical three-phase feeder or branch circuits.