Skip to main content
Siemens 3VA1125-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-4ED32-0AA0 SENTRON MCCB, 25 A, 3-Pole, 75.6

MPN3VA1125-4ED32-0AA0
Active

Siemens SENTRON 3VA1125-4ED32-0AA0, molded case circuit breaker, 3-pole, 25 A, TM210 thermal-magnetic release, 75.6 kA breaking capacity at 415 V AC, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1125-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1125-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.8.5 W

Protection & Trip Unit

3VA1125-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1125-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1125-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1125-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1125-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1125-4ED32-0AA0 — 25 A MCCB with TM210 Release

The Siemens SENTRON 3VA1125-4ED32-0AA0 is a three-pole molded case circuit breaker (MCCB) rated 25 A continuous at 40 °C, using a TM210 thermal-magnetic overcurrent release — that's a fixed thermal trip with magnetic short-circuit pickup, no adjustment dial. It's designed for line protection in distribution panels, not motor protection or adjustable overloads. Breaking capacity is where this part earns its keep: 75.6 kA at 415 V AC, 121 kA at 240 V AC, and still 11.9 kA at 690 V AC. That 75.6 kA figure at 415 V means it handles high-fault utility feeds without cascading upstream — a common requirement for main or tie breakers in industrial switchboards where the transformer secondary delivers heavy short-circuit current. Rated insulation voltage is 800 V. Front face carries IP40 protection.

Thermal Derating and Panel Fit

The 25 A rating holds flat from 40 °C through 50 °C, then drops to 24 A at 55–60 °C and 23 A at 65–70 °C. If your panel ambient runs above 50 °C, you lose 1–2 A of headroom — factor that into the load calculation, especially when the breaker feeds a subpanel near a heat source like a drive cabinet. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall. That 76.2 mm width is a standard 3-inch footprint for a 3-pole MCCB in this class — it clips onto a DIN rail or mounts with screws, and the 70 mm depth leaves room behind the gland plate for cable bends. No communication module, no undervoltage release, no ground-fault monitoring on this variant — it's a straight line-protection breaker.

Frequently asked questions

Does 3VA1125-4ED32-0AA0 have adjustable overload protection?

No — it uses a fixed TM210 thermal-magnetic release. Thermal trip and magnetic pickup are factory-set, not field-adjustable.

MPN
3VA1125-4ED32-0AA0