Siemens 3VA1125-4EE36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1125-4EE36-0AA0 MCCB, 25 A, 3-Pole, TM220

MPN3VA1125-4EE36-0AA0
Active

Siemens SENTRON 3VA1125-4EE36-0AA0, molded case circuit breaker, 3-pole, 25 A at 40 °C, TM220 overcurrent release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1125-4EE36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1125-4EE36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.8.5 W

Protection & Trip Unit

3VA1125-4EE36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1125-4EE36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1125-4EE36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1125-4EE36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1125-4EE36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1125-4EE36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated 25 A at 40 °C, built for line protection in distribution panels. It carries a TM220 thermal-magnetic overcurrent release — a fixed thermal trip with a magnetic short-circuit pickup that's adjustable across a 5–10x In range, giving you selectivity headroom on feeder circuits without swapping trip units. Breaking capacity runs 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V — numbers that cover most industrial service-entrance and sub-distribution applications. Rated insulation voltage is 800 V, so it's comfortable on 480/277 V and 600 V systems with margin. The front face carries IP40 protection — fine for a dry indoor panel; no washdown rating here. Power loss maxes at 8.5 W, which matters for thermal coordination in a densely packed enclosure.

Dimensions & Fit

The 3VA1125-4EE36-0AA0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that drops into Siemens SENTRON panelboards and most DIN-rail adapters. No undervoltage release, no communication module, no ground-fault monitoring; it's a straight thermal-magnetic breaker for straightforward line protection.

Frequently asked questions

Who supplies 3VA1125-4EE36-0AA0 and how is it quoted for volume purchases?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — quotes are confirmed at quote time.

What are the key ratings for 3VA1125-4EE36-0AA0?

Rated 25 A at 40 °C, 3-pole, with a TM220 thermal-magnetic release. Breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V. Rated insulation voltage is 800 V.

What is the depth of 3VA1125-4EE36-0AA0?

The depth is 70 mm (2.76 in).

What is the width of 3VA1125-4EE36-0AA0?

The width is 76.2 mm (3 in).