Skip to main content
Siemens 3VA1125-4EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-4EF32-0AD0 SENTRON MCCB, 25 A, 121 kA at 240

MPN3VA1125-4EF32-0AD0

Siemens SENTRON 3VA1125-4EF32-0AD0, 3-pole molded case circuit breaker, 25 A rated current, 121 kA breaking capacity at 240 VAC, TM240 thermal-magnetic release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1125-4EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11254EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1125-4EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.8.5 W
3VA1125-4EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1125-4EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1125-4EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1125-4EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1125-4EF32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1125-4EF32-0AD0 is a 3-pole molded case circuit breaker (MCCB) rated for 25 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release. Sized for line protection duty, meaning it's the primary overcurrent device on a feeder or branch circuit, not a motor-protective breaker with integrated overload class.

The SCCR curve drops predictably as voltage climbs: 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

Full 25 A rating holds through 50 °C ambient; above that it steps down: 24 A at 55–60 °C, 23 A at 65–70 °C. Mounting dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that fits most DIN-rail or direct-panel backplate layouts without re-drilling.

Frequently asked questions

What is the breaking capacity of 3VA1125-4EF32-0AD0 at 240 V?

121 kA at 240 VAC, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 500 V and 690 V.

Where can I buy 3VA1125-4EF32-0AD0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1125-4EF32-0AD0