Breaking capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V AC — figures that cover most industrial service-entrance and distribution panel fault levels.
Rated current holds at 25 A from 40 °C through 50 °C, then steps down to 24 A at 55–60 °C and 23 A at 65–70 °C. Physical envelope is 130 mm high, 76.2 mm wide, 70 mm deep; the width matches standard 3-pole MCCB cutouts in most Siemens SENTRON distribution boards.