Skip to main content
Siemens 3VA1125-4EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-4EF32-0JC0 SENTRON MCCB, 25 A, 121 kA at 240

MPN3VA1125-4EF32-0JC0

Siemens SENTRON 3VA1125-4EF32-0JC0, 3-pole molded case circuit breaker, 25 A at 40 °C, interrupting capacity 121 kA at 240 V, line protection, shunt trip (STL), 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1125-4EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11254EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1125-4EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.8.5 W

Protection & Trip Unit

3VA1125-4EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1125-4EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1125-4EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1125-4EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1125-4EF32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What the ratings mean for fit

The Siemens 3VA1125-4EF32-0JC0 is a 3-pole SENTRON molded case circuit breaker rated 25 A continuous at 40 °C, with full thermal current up to 50 °C before derating begins at 55 °C (24 A) and 65 °C (23 A). That means it holds its full rating across typical North American and European panel ambient conditions — no headroom lost until the enclosure runs hot. Interrupting capacity is 121 kA at 240 V, 75.6 kA at 415 V, and still 11.9 kA at 690 V. For a 25 A frame, those numbers are high — this breaker coordinates cleanly downstream of a larger upstream device without needing a current-limiting fuse ahead of it in most industrial distributions. Rated insulation voltage is 800 V, so it's rated for 690 V line-to-line systems common in European and Canadian industrial plants. The 70 mm depth and 76.2 mm width fit standard Siemens 3VA panel cutouts and DIN-rail adapters — no rework to drop it into an existing SENTRON lineup.

Line protection design — what it does and doesn't do

This breaker is designed for line protection — meaning it protects cables and busbars against overload and short circuit, not motors or generators. It ships with a shunt trip (STL) auxiliary release for remote tripping and two auxiliary switches (HQ) for status feedback to a PLC or indicator lamp. No undervoltage release, no ground-fault monitoring, no communication module — this is a straightforward thermal-magnetic MCCB for distribution panels where remote trip and contact status are the only extras needed.

Lifecycle and sourcing reality

Maximum power loss is 8.5 W, so thermal management in a dense panel is straightforward — no forced cooling required for this single breaker.

Panel integration notes

Mounts on DIN rail or direct panel. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. The 70 mm depth leaves clearance for standard 80 mm deep enclosures with wiring gutters. No trip indicator on the front face — status is read from the handle position or the auxiliary switches.

Frequently asked questions

Where can I buy 3VA1125-4EF32-0JC0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

What is the interrupting capacity of 3VA1125-4EF32-0JC0 at 415 V?

75.6 kA at 415 V, which covers most European industrial distribution fault levels without requiring a current-limiting upstream fuse.

Will 3VA1125-4EF32-0JC0 drop into a panel specified around 3VA1110-5ED36-0AC0?

Both are 3-pole SENTRON MCCBs with the same 70 mm depth and 76.2 mm width, so the mechanical fit is identical. The functional difference is rating — the 3VA1125-4EF32-0JC0 carries 25 A continuous versus the 3VA1110 frame's lower rating, and interrupting capacities differ. Verify the fault-current study before swapping.

MPN