SENTRON 3VA1125-5ED22-0AA0 — 25 A, 2-Pole MCCB with TM210 Release
Rated current holds at 25 A from 40 °C through 50 °C ambient, then derates to 24 A at 55–60 °C and 23 A at 65–70 °C. In a hot panel — say, next to a transformer or in a non-ventilated enclosure — the 23 A limit at 70 °C is the number to use for your load calculation, not the 25 A nameplate. Operating voltage is 415 V AC or 250 V DC; insulation voltage is rated 500 V. Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — a standard 2-pole MCCB footprint that fits most DIN-rail or panel-mount bases in the SENTRON range.