MCCB for high-fault panel builds
At 440 V it still holds 75.6 kA, dropping to 17 kA at 500 V and 690 V. Four poles let it switch three-phase plus neutral in a single envelope, saving a DIN row over separate breakers.
The 25 A rating holds flat from 40 °C to 50 °C; above that it derates to 24 A at 55 °C and 60 °C, then 23 A at 65 °C and 70 °C. A panel OEM wiring a 24 A continuous load at 60 °C ambient needs to account for that step-down. Front IP40 protects against tool drops and dust ingress; the body is open-frame behind the panel, so clearance to live parts follows local wiring rules.