Siemens 3VA1125-5EF32-0BH0 SENTRON MCCB, 25 A, 187 kA at 240

MPN3VA1125-5EF32-0BH0

Siemens SENTRON 3VA1125-5EF32-0BH0, molded case circuit breaker, 3-pole, 25 A, 187 kA breaking capacity at 240 V AC, TM240 thermal-magnetic release, with undervoltage release and auxiliary contacts.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1125-5EF32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1125-5EF32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C23.5 A
Current at 65 °C23 A
Current at 70 °C22.5 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1125-5EF32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1125-5EF32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1125-5EF32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1125-5EF32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1125-5EF32-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Thermal derating and ambient temperature

The 3VA1125-5EF32-0BH0: The breaker holds its full 25 A rating up to 50 °C ambient. Above that, it derates linearly: 24 A at 55 °C, 23.5 A at 60 °C, 23 A at 65 °C, and 22.5 A at 70 °C. If your panel runs hot — near a drive or transformer — factor that curve into the load schedule; the 25 A nameplate applies only below 50 °C.

Integrated undervoltage release and auxiliary contacts

This variant includes an undervoltage release (UVR) as the auxiliary release design, plus a 2 auxiliary switch + 1 trip alarm switch HQ contact block. The UVR trips the breaker when control voltage drops below a threshold — standard for safety circuits where loss of control power must open the main contacts. The auxiliary contacts feed status back to a PLC or annunciator panel without a separate interposing relay.

Panel fit and dimensions

The 3VA1125-5EF32-0BH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a 3-pole footprint that fits standard SENTRON mounting plates and DIN-rail adapters. IP40 on the front face means it is protected against tools and wires >1 mm, suitable for enclosed distribution boards; no washdown rating, so keep it inside the cabinet.

Frequently asked questions

Where can I buy 3VA1125-5EF32-0BH0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time.

What is the breaking capacity of 3VA1125-5EF32-0BH0 at different voltages?

187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — these are the interrupting ratings that govern selectivity coordination in high-fault panels.

Does 3VA1125-5EF32-0BH0 include an undervoltage release?

Yes, the auxiliary release design is an undervoltage release (UVR), which opens the breaker when control voltage drops below the dropout threshold.