Siemens SENTRON 3VA1125-5EF32-0KA0 – 25 A MCCB with Shunt Trip
Rated current is 25 A up to 50 °C, derating to 23 A at 70 °C. The 187 kA breaking capacity at 240 V AC drops to 121 kA at 415 V and 75.6 kA at 440 V; at 500 V and 690 V it holds at 17 kA — sufficient for high-fault industrial panels where selectivity with upstream gear matters. The shunt trip (STL) allows remote tripping from an emergency-stop or safety circuit — useful for a controlled disconnection under fault or maintenance conditions.
Panel Integration & Mounting
The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep; the 3-inch width fits standard panel cutouts for 3-pole MCCBs.