Skip to main content
Siemens 3VA1125-6EF32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-6EF32-0AG0 SENTRON MCCB, 25 A, 220 kA at 240

MPN3VA1125-6EF32-0AG0

Siemens SENTRON 3VA1125-6EF32-0AG0, molded case circuit breaker, 3-pole, 25 A rated at 40 °C, 220 kA breaking capacity at 240 V, line protection design, with auxiliary switch and trip alarm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1125-6EF32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11256EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA1125-6EF32-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.8.5 W
3VA1125-6EF32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1125-6EF32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1125-6EF32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1125-6EF32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1125-6EF32-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1125-6EF32-0AG0 — 25 A MCCB for Line Protection

It carries a continuous current rating of 25 A at 40 °C, derating to 23 A at 70 °C — the thermal-magnetic TM240 release handles overload and short-circuit protection without external auxiliaries. Breaking capacity is the standout: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V. That puts this MCCB in the high-interrupting class — suitable for installations with high available fault current, such as industrial main switchboards or transformer secondaries where selectivity with downstream breakers is critical. The 3-pole frame is 76.2 mm wide, 130 mm tall, 70 mm deep — a standard SENTRON 3VA1 footprint that fits existing panel layouts without re-drilling.

Integration and Panel Fit

No undervoltage release or shunt trip is included — those are separate accessories if needed.

MPN
3VA1125-6EF32-0AG0