Skip to main content
Siemens 3VA1125-6GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-6GD42-0AA0 SENTRON MCCB, 25 A, 4-Pole, 220 k

MPN3VA1125-6GD42-0AA0
Active

Siemens SENTRON 3VA1125-6GD42-0AA0, molded case circuit breaker, 4-pole, 25 A, TM210 trip unit, 220 kA at 240 VAC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1125-6GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1125-6GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.8.5 W
3VA1125-6GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1125-6GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1125-6GD42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1125-6GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1125-6GD42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

It is designed for distribution and branch-circuit protection in commercial and industrial panels where high fault current capability is required. Its breaking capacity reaches 220 kA at 240 VAC, 154 kA at 415 VAC, and 121 kA at 440 VAC — figures that place it in the high-interrupting range for a 25 A frame, suitable for installations with large upstream transformers or high available fault current. At 500 VAC and 690 VAC the breaking capacity is 17 kA, so the voltage rating of the supply must be checked against the available fault current before specifying.

At 55 °C it derates to 24 A, at 65 °C to 23 A, and at 70 °C to 23 A — a shallow curve that keeps most panel applications at the nameplate rating. Front IP40 protection covers the operator interface.

Frequently asked questions

What trip unit does this breaker use?

It is fitted with a TM210 thermal-magnetic overcurrent release, designed for line protection without undervoltage release or communication functions.

MPN
3VA1125-6GD42-0AA0