Skip to main content
Siemens 3VA1125-6GD46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1125-6GD46-0AA0 SENTRON MCCB, 25 A, 4-Pole, 220 k

MPN3VA1125-6GD46-0AA0
Active

Siemens SENTRON 3VA1125-6GD46-0AA0, molded case circuit breaker, 4-pole, 25 A rated, TM210 thermal-magnetic trip, breaking capacity 220 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1125-6GD46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1125-6GD46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.8.5 W

Protection & Trip Unit

3VA1125-6GD46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1125-6GD46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1125-6GD46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1125-6GD46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1125-6GD46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

What this MCCB is and what the ratings mean

The Siemens 3VA1125-6GD46-0AA0 is a SENTRON-series molded case circuit breaker (MCCB) for line protection — the main disconnect and fault interrupter in a distribution panel, motor control center, or feeder circuit. It is a 4-pole device rated 25 A continuous, meaning it protects a 25 A branch circuit and will not nuisance-trip at that load under normal conditions. The breaking capacity is where this part earns its place: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V. Those numbers tell you it can safely interrupt a fault current up to those levels at the respective system voltage — critical for high-fault installations like large transformer secondaries or industrial substations where available fault current exceeds standard 65 kA or 100 kA breakers. The TM210 designation means a thermal-magnetic trip unit — the thermal element handles overload protection (time-curve shaped), and the magnetic element handles instantaneous short-circuit protection. No undervoltage release, no shunt trip, no communication module on this variant; it is a straight, hardwired line-protection breaker.

Panel fit and thermal derating

Dimensions: 130 mm tall, 101.6 mm wide, 70 mm deep. That 70 mm depth is the can depth behind the panel face — important for gland-plate clearance and busbar stacking in a shallow enclosure. The 4-pole width (101.6 mm) is roughly 4 inches, standard for a 4-pole MCCB frame; verify the DIN-rail or mounting-plate pattern matches your existing backpanel layout. Thermal derating is minimal for this frame: it carries the full 25 A from 40 °C through 50 °C ambient, then drops only to 24 A at 55 °C and 60 °C, and 23 A at 65 °C and 70 °C. In a hot panel — near a transformer or in a non-climate-controlled enclosure — you lose only 1–2 A before the trip curve shifts. Maximum power loss is 8.5 W, so the breaker itself does not add significant heat to the enclosure. Front protection is IP40 — finger-safe from the front but not sealed against dust ingress. Not for washdown or outdoor exposure without an additional enclosure. Storage range is -40 °C to 80 °C; operating ambient is -25 °C to 70 °C.

Frequently asked questions

What is the breaking capacity of the 3VA1125-6GD46-0AA0 at different voltages?

Breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at both 500 V and 690 V.

What is the rated current and number of poles?

Rated current is 25 A continuous, and it is a 4-pole device.

Where can I buy the 3VA1125-6GD46-0AA0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1125-6GD46-0AA0