The rated current In is 25 A, with overload protection adjustable from 18 A to 25 A and short-circuit protection set between 6.4 and 12.8 times In. This variant includes 100% N conductor protection and a nut keeper kit, specified for a DC Power OEM in China.
The TM240 thermal-magnetic trip gives a fixed magnetic pickup, so coordination studies need to account for the 6.4–12.8x In range. The nut keeper kit is a mechanical accessory for secure mounting in OEM builds.