3VA1132-3ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1132-3ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W
3VA1132-3ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1132-3ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1132-3ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1132-3ED32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 32 A at 40 °C with a TM210 thermal-magnetic overcurrent release, designed for line protection in distribution panels and industrial switchboards.

Rated 32 A continuously at ambient temperatures up to 50 °C (–), derating to 30 A at 65–70 °C (–). That thermal curve matters when you pack breakers side-by-side in a hot enclosure — the TM210 release holds its trip characteristic across that range, but the continuous current limit drops. Breaking capacity varies with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V or 690 V (–). That means it handles high fault currents on 240 V services but needs coordination upstream for 690 V applications where the available fault current exceeds 11.9 kA.

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — standard 3-pole MCCB footprint for DIN-rail or screw-mount installation in a distribution board.

Frequently asked questions

Where can I buy 3VA1132-3ED32-0AA0 and how is it quoted?

This MCCB is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not before.

What is the breaking capacity of this MCCB at 240 V?

75.6 kA at 240 V, which covers most North American 240/120 V panelboard applications. At 415 V it's 52.5 kA, and at 690 V it drops to 11.9 kA.

Will 3VA1132-3ED32-0AA0 drop into a panel specified around 6ES7514-2DN03-0AB0 without rewiring?

No — 6ES7514-2DN03-0AB0 is a Siemens S7-1500 CPU module, not a circuit breaker. They serve completely different functions and footprints. This MCCB replaces another 3VA or comparable 3-pole MCCB, not a PLC.