Specifications

Identification

3VA1132-3EF32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11323EF320AA0

Ratings

3VA1132-3EF32-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-3EF32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-3EF32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-3EF32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-3EF32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-3EF32-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1132-3EF32-0JA0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for 32 A at 40 °C, with a TM240 thermal-magnetic overcurrent release and an integrated shunt trip (STL) auxiliary release. It is designed for line protection in distribution panels and motor control centers, where the shunt trip allows remote or emergency-off tripping via a control voltage. Breaking capacity reaches 75.6 kA at 240 V AC, 52.5 kA at 415 V, and 32 kA at 440 V, tapering to 11.9 kA at both 500 V and 690 V. This SCCR profile covers most industrial low-voltage fault levels, and the 800 V rated insulation voltage confirms suitability for 690 V systems with adequate clearance.

Thermal derating and panel fit

At 55 °C the continuous rating derates to 31 A, and at 65 °C to 30 A. The 70 mm depth and 76.2 mm width fit standard 3-pole MCCB mounting footprints in distribution boards; the 130 mm height leaves clearance for cable entry from above or below. Maximum power loss is 10.6 W. In a sealed enclosure with multiple breakers ganged, this heat adds up — account for it in the thermal budget, especially above 50 °C where the derating curve starts to bite.

Sourcing and lifecycle

For a BOM line that needs this exact shunt-trip variant, the order code is the one to specify — the base breaker without the shunt trip is a different code, and adding a field-installed shunt trip later costs more in labor and panel rework.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V (–). The 800 V rated insulation voltage supports use on 690 V systems.

What is the shunt trip release on this breaker for?

The integrated shunt trip (STL) allows remote tripping by applying a control voltage — used for emergency-off circuits, interlocking with fire alarms, or PLC-based shutdown sequences.

Where can I buy 3VA1132-3EF32-0JA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1132-3EF32-0JA0