Siemens 3VA1132-3EF32-0JH0 SENTRON MCCB, 32 A, 3-Pole, 75.6

MPN3VA1132-3EF32-0JH0

Siemens SENTRON 3VA1 series, Molded Case Circuit Breaker, 3VA1132-3EF32-0JH0, 3-pole, 32 A rated, TM240 thermal-magnetic release, interrupting 75.6 kA at 240 V, 52.5 kA at 415 V, shunt trip, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1132-3EF32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1132-3EF32-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1132-3EF32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1132-3EF32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3EF32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1132-3EF32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3EF32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1132-3EF32-0JH0 — 32 A MCCB, Line Protection, Active Production

The interrupting ratings climb with applied voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — figures that cover most industrial distribution panels up to 690 V line-to-line.

The thermal-magnetic release (TM240) is non-adjustable — set at the factory for 32 A at 40 °C ambient, and it holds 32 A all the way up to 50 °C; above that it starts a gentle thermal derating curve (30.72 A at 55 °C, down to 28.8 A at 70 °C).

Auxiliaries and Releases — What's Onboard

The integrated auxiliary trip module carries its own order code (3VA9688-0BL32) for replacement reference.

MPN