Skip to main content
Siemens 3VA1132-3EF36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-3EF36-0BA0 SENTRON MCCB, 32 A, 3-Pole, 75.6

MPN3VA1132-3EF36-0BA0

Siemens SENTRON 3VA1132-3EF36-0BA0, molded case circuit breaker, 3-pole, 32 A rated at 40 °C, TM240 overcurrent release, 75.6 kA breaking capacity at 240 V, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-3EF36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11323EF360AA0

Ratings

3VA1132-3EF36-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.13.1 W

Protection & Trip Unit

3VA1132-3EF36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-3EF36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-3EF36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-3EF36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-3EF36-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1132-3EF36-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated 32 A at 40 °C, with a TM240 thermal-magnetic overcurrent release and an integrated undervoltage release. Its 75.6 kA interrupting capacity at 240 V gives it headroom for high-fault service-entrance or distribution panels where the available fault current is substantial.

Breaking capacity and selectivity

At 240 V the breaker clears 75.6 kA; at 415 V it's rated 52.5 kA, dropping to 32 kA at 440 V and 11.9 kA at 500 V and 690 V. Those figures govern the upstream transformer and bus bracing — the 75.6 kA at 240 V means it can sit behind a typical 150 kVA or larger transformer without cascading. The 800 V rated insulation voltage supports 480 V delta or 600 V wye systems with margin.

Thermal derating and panel fit

Rated current holds at 32 A up to 50 °C ambient, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C. In a sealed, uncooled enclosure at 55 °C the breaker still carries 31 A continuous — useful for a crowded panel. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall, fitting standard 3-pole MCCB mounting footprints. Maximum power loss is 13.1 W, which factors into enclosure thermal calculations.

Frequently asked questions

Where can I buy 3VA1132-3EF36-0BA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings of 3VA1132-3EF36-0BA0?

It is a 3-pole MCCB rated 32 A at 40 °C with a TM240 thermal-magnetic release, an undervoltage release, and a breaking capacity of 75.6 kA at 240 V.

What is the breaking capacity at different voltages?

At 240 V it clears 75.6 kA, at 415 V it clears 52.5 kA, at 440 V it clears 32 kA, and at 500 V and 690 V it clears 11.9 kA.

Does the 3VA1132-3EF36-0BA0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release.

MPN
3VA1132-3EF36-0BA0