It carries a continuous current Iu of 32 A at 40 °C through 50 °C, derating to 30.72 A at 55 °C and 28.8 A at 70 °C — a thermal curve that matters for panel fill factor and ambient placement. The TM240 thermal-magnetic release handles overload and short-circuit response without an electronic trip unit, keeping the design simple for distribution panels that don't need adjustable curves. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V — these are the fault-clearing numbers that govern SCCR coordination downstream. For DC network applications, the manufacturer directs to the 3VA device manual for switching power values; the part itself is not pre-rated for DC in the basic listing.
Depth is 70 mm, height 130 mm. No communication module, no voltage trigger, no phase failure detection — this is a plain line-protection breaker, not a metering or communicating device.