Rated 32 A continuous at ambient temperatures up to 50 °C without derating; at 55 °C it carries 31 A, and at 70 °C it holds 30 A — so in a warm panel you lose only 2 A off the nameplate. Breaking capacity is 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V — high enough for most distribution panels fed by a transformer of 1000 kVA or less without needing a current-limiting upstream breaker.
Three-pole configuration, 76.2 mm wide (roughly 3 inches), 130 mm tall, 70 mm deep — fits standard MCCB mounting footprints and leaves room for auxiliary wiring alongside. Max power dissipation is 10.6 W — negligible for panel thermal budgeting, but worth noting if you pack multiple breakers in a sealed enclosure.
Operating environment and lifecycle
Includes a mechanical trip indicator for visual fault confirmation without opening the panel door.
Sourcing and compliance
Standard compliance documentation applies; request specific certificates with your RFQ.