Skip to main content
Siemens 3VA1132-3EF36-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1132-3EF36-0JH0 MCCB, 32 A, 3-Pole, 75.6

MPN3VA1132-3EF36-0JH0

Siemens SENTRON 3VA1132-3EF36-0JH0, 3-pole molded case circuit breaker, 32 A rated at 40 °C, breaking capacity 75.6 kA at 240 V, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-3EF36-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11323EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1132-3EF36-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-3EF36-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-3EF36-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-3EF36-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1132-3EF36-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-3EF36-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1132-3EF36-0JH0 — 32 A MCCB, Line Protection, Active Production

The Siemens SENTRON 3VA1132-3EF36-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated 32 A at 40 °C, designed for line protection in distribution panels. Breaking capacity reaches 75.6 kA at 240 VAC, 52.5 kA at 415 VAC, and 32 kA at 440 VAC — sufficient for high-fault industrial mains or sub-distribution boards where the available fault current is known to be elevated. Rated insulation voltage is 800 V, and maximum power loss is 10.6 W. It ships with a shunt trip (STL) release and a 2 auxiliary switch + 1 trip alarm switch HQ configuration, which simplifies integration into safety circuits or remote-trip indication loops — no separate aux block kit to order.

Mounting and Panel Fit

Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — fits standard MCCB mounting footprints in Siemens SENTRON distribution boards or third-party enclosures with compatible cutouts. Operating temperature range is -25 °C to +70 °C; storage range -40 °C to +80 °C. Current rating holds flat at 32 A from 40 °C to 50 °C, then derates to 30 A at 70 °C — no derating penalty in typical 40 °C panel ambient.

Frequently asked questions

What auxiliary switches and releases come with this MCCB?

It includes 2 auxiliary switches plus 1 trip alarm switch HQ, and a shunt trip (STL) release — no separate aux block to order.

MPN
3VA1132-3EF36-0JH0