Skip to main content
Siemens 3VA1132-4EF32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF32-0AC0 SENTRON MCCB, 32 A, 3-Pole, 121 k

MPN3VA1132-4EF32-0AC0

Siemens SENTRON 3VA1132-4EF32-0AC0, molded case circuit breaker, 3-pole, 32 A (rated at 40-50 °C), 121 kA breaking capacity at 240 VAC, TM240 thermal-magnetic release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11324EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1132-4EF32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-4EF32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4EF32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1132-4EF32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What this MCCB delivers on the panel

The Siemens 3VA1132-4EF32-0AC0 is a SENTRON molded case circuit breaker (MCCB) built for line protection in distribution panels. Its 32 A rating holds across 40 °C to 50 °C ambient, then derates to 30 A at 70 °C — so in a warm enclosure you still get full rated current up to 50 °C, which is the typical panel interior temperature under load. Breaking capacity is the headline: 121 kA at 240 VAC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 121 kA figure at 240 V means it can interrupt a fault current up to that level without rupturing — critical for high-fault-capacity service entrances or transformer secondaries where the available fault current is high. The TM240 thermal-magnetic release gives fixed thermal and magnetic trip settings tuned for cable and busbar protection. Insulation voltage is rated 800 V, so the breaker is comfortable on 480/277 V or 600 V systems with headroom.

Physical fit and auxiliary options

Three-pole design, 76.2 mm wide, 130 mm tall, 70 mm deep — standard MCCB footprint for a 32 A frame. Mounts on a DIN rail or panel-mount via the SENTRON base. The 2 auxiliary switches (HQ type) are built in, so you get status feedback without an external add-on block. Power loss is 10.6 W maximum — negligible for thermal budgeting in a populated panel, but worth noting if you are packing breakers tightly in a sealed enclosure.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

121 kA at 240 VAC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

How do I get pricing and availability for this part?

Submit an RFQ through this listing. We source the part to order and confirm current pricing and availability at quote time.

What type of overcurrent release does this breaker use?

It uses a TM240 thermal-magnetic release — fixed thermal and magnetic trip settings for line protection.

MPN
3VA1132-4EF32-0AC0