Siemens 3VA1132-4EF32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF32-0CH0 SENTRON MCCB, 32 A, 121 kA at 240

MPN3VA1132-4EF32-0CH0

Siemens SENTRON 3VA1132-4EF32-0CH0, molded case circuit breaker, 3-pole, 32 A rated continuous current Iu, interrupting 121 kA at 240 V, TM240 thermal-magnetic release, IP40 front protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1132-4EF32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1132-4EF32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1132-4EF32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1132-4EF32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF32-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What the interrupting ratings mean for panel coordination

The Siemens SENTRON 3VA1132-4EF32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 32 A continuous current (Iu) at 40 °C through 50 °C ambient, with a slight thermal derating curve above that — 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. The interrupting capacity is the headline: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. For a panel designer, the 121 kA at 240 V means this breaker can be placed at the main service entrance on a high-fault utility feed without needing upstream current-limiting fuses — it clears a bolted fault at that level in its own arc chamber. The 75.6 kA at 415 V covers most European industrial distribution boards. The 690 V figure (11.9 kA) is lower but still adequate for motor control centers where the transformer impedance limits available fault current to well under that.

TM240 release and auxiliary configuration

The overcurrent release is the TM240 thermal-magnetic type — fixed thermal pickup at 32 A, magnetic short-circuit trip set at the factory. This is a line-protection MCCB, not a motor-protection breaker; the TM240 curve is optimized for cable and busbar protection, not for motor inrush. The auxiliary contact block is factory-fitted as 2 auxiliary switches plus 1 trip alarm switch (HQ type), and the integrated undervoltage release (UVR) is wired to the coil terminals. The UVR part number for the auxiliary trip is 3VA9608-0BB24. No ground-fault monitoring, no communication module, no voltage-trip function — this is a straightforward thermal-magnetic breaker for fixed-distribution panels.

Panel integration and mounting dimensions

The breaker measures 76.2 mm wide, 130 mm high, and 70 mm deep. It mounts on a DIN rail or directly to a backplate via screw terminals. The IP40 rating on the front means it is protected against solid objects larger than 1 mm (tools, wires) but not against water ingress — suitable for indoor panel installation, not washdown environments. The 3-pole design with the factory-fitted auxiliary contacts and UVR occupies a fixed footprint; no additional modules are needed for the basic trip and alarm functions. The rated insulation voltage (Ui) is 800 V, which covers 690 V systems with margin.

Frequently asked questions

Where can I buy 3VA1132-4EF32-0CH0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the interrupting ratings for 3VA1132-4EF32-0CH0?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

What is the continuous current rating and thermal derating?

Rated 32 A continuous (Iu) at 40 °C through 50 °C ambient, derating to 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C.

What auxiliary contacts and releases are fitted?

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ type) and an integrated undervoltage release (UVR). The UVR auxiliary trip part is 3VA9608-0BB24.

MPN