Skip to main content
Siemens 3VA1132-4EF32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1132-4EF32-0DC0 MCCB, 32 A, 3-Pole, 121 k

MPN3VA1132-4EF32-0DC0

Siemens SENTRON 3VA1132-4EF32-0DC0, molded case circuit breaker, 3-pole, 32 A (40 °C), interrupting rating 121 kA at 240 V AC, line protection, undervoltage release, 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11324EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1132-4EF32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.13.1 W

Protection & Trip Unit

3VA1132-4EF32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4EF32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1132-4EF32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens SENTRON 3VA1132-4EF32-0DC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection — the main feeder or branch protection in a distribution panel. It carries a continuous current of 32 A at 40 °C ambient, and derates to 30 A at 70 °C if the panel runs hot. The interrupting rating hits 121 kA at 240 V AC, which means it can clear a bolted fault at that level without the arc re-striking or the case rupturing — important when the available fault current at the panel is high. This MCCB includes an undervoltage release (UVR) and two auxiliary switches (HQ design) for remote status feedback. The UVR trips the breaker if the control voltage drops below a set threshold — common in emergency-stop chains or when a loss-of-voltage condition must open the circuit automatically. The auxiliary switches give a dry-contact signal back to a PLC or annunciator panel. The insulation voltage is rated 800 V, so it can sit on a 690 V line with margin. The interrupting curve drops to 11.9 kA at 500 V and 690 V — still enough for most industrial motor branch circuits, but worth checking against the transformer nameplate if you're feeding a 690 V drive.

Mounting and panel fit

The 3VA1132-4EF32-0DC0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep. The 76.2 mm width fits a standard 3-pole MCCB footprint.

Frequently asked questions

Does 3VA1132-4EF32-0DC0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) plus two auxiliary switches (HQ design). The UVR trips the breaker if control voltage drops below a set threshold.

MPN
3VA1132-4EF32-0DC0