Skip to main content
Siemens 3VA1132-4EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF32-0HA0 SENTRON MCCB, 32 A, 121 kA at 240

MPN3VA1132-4EF32-0HA0

Siemens SENTRON 3VA1132-4EF32-0HA0, 3-pole molded case circuit breaker, 32 A rated continuous current, 121 kA breaking capacity at 240 V, TM240 thermal-magnetic release, shunt trip, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1132-4EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1132-4EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1132-4EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-4EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF32-0HA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB delivers

The Siemens 3VA1132-4EF32-0HA0 is a 3-pole SENTRON molded case circuit breaker rated for line protection at 32 A continuous current (Iu). Its TM240 thermal-magnetic release handles overload and short-circuit protection without communication or phase-failure detection — a straightforward, non-communicating MCCB for standard distribution panels. Breaking capacity climbs to 121 kA at 240 V, drops to 75.6 kA at 415 V, and holds 52.5 kA at 440 V — figures that cover most industrial service-entrance and sub-distribution applications. At 690 V it still interrupts 11.9 kA, useful for high-voltage motor circuits in 690 V plants.

Thermal derating and panel fit

Full 32 A rating holds through 50 °C ambient; above that it derates to 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. If the panel runs hot — say, a packed enclosure near a process line — factor the 55 °C or 60 °C row into the load schedule rather than the 32 A nameplate. Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep — a standard 3-pole MCCB width that fits most DIN-rail or mounting-plate layouts. IP40 on the front means it's protected against tools and wires >1 mm but not against water; keep it inside a rated enclosure.

Auxiliary trip and release options

This variant ships with a shunt trip (STL) for remote tripping — the integrated auxiliary release is order code 3VA9688-0BL30. No undervoltage release, no auxiliary contact, no ground-fault monitoring. If the BOM calls for UVR or a status contact, this isn't the version; look at the 3VA11.. family with the appropriate suffix.

MPN
3VA1132-4EF32-0HA0