Skip to main content
Siemens 3VA1132-4EF32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF32-0JA0 SENTRON MCCB, 32 A, 3-Pole, 121 k

MPN3VA1132-4EF32-0JA0

Siemens SENTRON 3VA1132-4EF32-0JA0, molded case circuit breaker (MCCB), 3-pole, rated current 32 A, breaking capacity 121 kA at 240 V, 75.6 kA at 415 V, line protection design, shunt trip release (STL).

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11324EF320AA0

Ratings

3VA1132-4EF32-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-4EF32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4EF32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-4EF32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF32-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1132-4EF32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 32 A continuous current at 40 °C, with a thermal-magnetic overcurrent release (TM240). Its interrupting capacity hits 121 kA at 240 V AC and 75.6 kA at 415 V AC — high enough for most distribution and motor branch circuits in industrial panels. The shunt trip release (STL) allows remote tripping via a control voltage, which simplifies emergency-stop integration or load-shedding schemes.

Breaking capacity and thermal performance

The 121 kA at 240 V and 75.6 kA at 415 V mean this breaker can safely clear high-fault currents typical near large transformers or busway taps — no need for upstream current-limiting fuses in most panels. At 690 V the capacity drops to 11.9 kA, still adequate for motor circuits with dedicated short-circuit protection. The thermal derating is shallow: it holds 32 A from 40 °C to 50 °C, then drops only to 30 A at 70 °C. That gives headroom in warm enclosures without oversizing.

Panel fit and integration

The 3VA1132-4EF32-0JA0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mount panel layouts. The shunt trip release (STL) occupies the auxiliary slot, so no extra external relay is needed for remote trip. Rated insulation voltage is 800 V, which covers 480 V and 600 V class systems with margin.

Frequently asked questions

What is the breaking capacity of 3VA1132-4EF32-0JA0 at 415 V?

75.6 kA at 415 V AC. This rating is sufficient for most industrial distribution panels and motor branch circuits.

Where can I buy 3VA1132-4EF32-0JA0 and get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

Does 3VA1132-4EF32-0JA0 include a shunt trip?

Yes, it is fitted with a shunt trip release (STL) for remote tripping via a control voltage. No undervoltage release is included.

What is the rated current of 3VA1132-4EF32-0JA0 at elevated temperatures?

Rated 32 A continuously at 40 °C, 45 °C, and 50 °C. It derates to 31 A at 55 °C and 60 °C, and to 30 A at 65 °C and 70 °C.

MPN
3VA1132-4EF32-0JA0