Skip to main content
Siemens 3VA1132-4EF36-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF36-0JC0 SENTRON MCCB, 3-Pole, 32 A, 121 k

MPN3VA1132-4EF36-0JC0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1132-4EF36-0JC0, 3-pole, 32 A, line protection, breaking capacity 121 kA at 240 V AC, 75.6 kA at 415 V, with shunt trip (STL) and 2 auxiliary switches HQ, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF36-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11324EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1132-4EF36-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-4EF36-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4EF36-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF36-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1132-4EF36-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF36-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens 3VA1132-4EF36-0JC0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in distribution panels. Its 3-pole construction and 32 A rating (continuous at 40 °C through 50 °C, derating to 30 A at 70 °C) make it a fit for feeder or branch circuits in commercial and industrial switchboards.

Breaking capacity — the real-world fault stop

This MCCB carries a breaking capacity of 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Those numbers define the maximum fault current it can safely interrupt at each system voltage — critical for selectivity studies and SCCR compliance in panels feeding motor control centers or high-fault transformer secondaries.

Thermal derating and panel integration

Rated 32 A continuous from 40 °C to 50 °C, it derates to 31 A at 55–60 °C and 30 A at 65–70 °C. In a closed panel with multiple breakers ganged, that derating curve governs the real ampacity — don't load it to 32 A if ambient inside the enclosure hits 55 °C. Dimensions are 130 mm tall, 76.2 mm wide, and 70 mm deep, fitting standard 3-pole MCCB footprints on DIN rail or panel-mount backplates.

Auxiliaries and release options

Factory-fitted with a shunt trip (STL) for remote opening and two HQ auxiliary switches for status feedback to a PLC or alarm circuit. Rated insulation voltage is 800 V, and maximum power loss is 10.6 W per pole — relevant for thermal budgeting in densely populated panels.

Frequently asked questions

Where can I buy 3VA1132-4EF36-0JC0 and how do I get a price?

This MCCB is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing.

What is the breaking capacity of 3VA1132-4EF36-0JC0 at different voltages?

121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

Does 3VA1132-4EF36-0JC0 include a shunt trip or auxiliary switches?

Yes, it comes with a shunt trip (STL) for remote opening and two HQ auxiliary switches for status signaling.

MPN