Skip to main content
Siemens 3VA1132-4EF46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4EF46-0AA0 SENTRON MCCB, 4P, 32A, 121kA at 2

MPN3VA1132-4EF46-0AA0
Active

Siemens SENTRON 3VA1132-4EF46-0AA0, 4-pole molded case circuit breaker, 32 A rated, TM240 thermal-magnetic trip, 121 kA at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4EF46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1132-4EF46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-4EF46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4EF46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4EF46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-4EF46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4EF46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

MCCB for line protection — 32 A, 4-pole, high breaking capacity

The Siemens SENTRON 3VA1132-4EF46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 32 A continuous at 40 °C, with a TM240 thermal-magnetic trip unit designed for line protection — meaning it protects cables and distribution buswork from overload and short-circuit faults, not motor loads. The 121 kA breaking capacity at 240 V gives substantial SCCR headroom for high-fault panels; at 415 V it still interrupts 75.6 kA, and at 690 V it holds 11.9 kA. The 32 A rating holds steady through 50 °C, then derates to 30 A at 70 °C — useful for panels with elevated internal ambient.

Integration — panel fit and mounting

The 3VA1132-4EF46-0AA0 mounts on a DIN rail or can be screw-fixed to a backplate. Its 101.6 mm width (4 in) and 70 mm depth (2.76 in) fit standard MCCB panel cutouts; height is 130 mm (5.12 in). IP40 on the front means it is protected against tools and small wires entering from the front, but the enclosure must provide overall panel IP rating. No undervoltage release, no communication module, no ground-fault monitoring — it is a straight thermal-magnetic breaker for basic line protection.

Frequently asked questions

Who supplies 3VA1132-4EF46-0AA0 and how is it quoted for volume purchases?

This MCCB is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is 3VA1132-4EF46-0AA0's breaking capacity at different voltages?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

What is the temperature derating for this 32 A MCCB?

Rated 32 A continuous from 40 °C to 50 °C, then derates to 31 A at 55–60 °C, and 30 A at 65–70 °C.

MPN
3VA1132-4EF46-0AA0