Skip to main content
Siemens 3VA1132-4GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-4GD42-0AA0 SENTRON MCCB, 32 A, 4-Pole, TM210

MPN3VA1132-4GD42-0AA0
Active

Siemens SENTRON 3VA1132-4GD42-0AA0, molded case circuit breaker, 4-pole, 32 A, TM210 overcurrent release, line protection, breaking capacity 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-4GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA1132-4GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-4GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1132-4GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-4GD42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-4GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-4GD42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1132-4GD42-0AA0 — 32 A 4-Pole MCCB with TM210 Release

The Siemens 3VA1132-4GD42-0AA0 is a SENTRON-series molded case circuit breaker (MCCB) rated for line-protection duty, carrying a continuous current of 32 A across all four poles. Its TM210 thermal-magnetic overcurrent release provides fixed thermal and magnetic trip settings — no interchangeable trip units, which simplifies specification for a fixed-load panel. The 4-pole configuration suits three-phase systems with a fully switched neutral, common in North American and IEC distribution boards where neutral isolation is required. Breaking capacity is the headline selection parameter here: 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. For a 32 A frame, these figures place it in the high-interrupting category — it can clear a fault on a large transformer secondary or a high-capacity bus without upstream coordination issues. The 121 kA at 240 V is particularly relevant for 120/240 V split-phase services in commercial buildings where available fault current can exceed 100 kA near the service entrance. Thermal derating is minimal up to 50 °C (full 32 A), then drops to 31 A at 55–60 °C and 30 A at 65–70 °C. This flat curve means the breaker can be packed into a warm enclosure without significant de-rating — useful for high-density panel layouts. Rated insulation voltage is 800 V, and maximum power loss is 10.6 W, which factors into enclosure heat-load calculations.

Integration and Mounting

Dimensions are 70 mm depth, 101.6 mm width, 130 mm height — a compact 4-pole footprint that fits standard Siemens 3VA mounting accessories. Front-face protection class is IP40, suitable for enclosed panel mounting where no water ingress is expected. The TM210 release is factory-set and non-interchangeable, so verify the 32 A rating matches the downstream load before panel assembly; no field calibration is possible.

Frequently asked questions

What is the breaking capacity of 3VA1132-4GD42-0AA0 at different voltages?

Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

What overcurrent release does the 3VA1132-4GD42-0AA0 use?

It uses a TM210 thermal-magnetic overcurrent release with fixed settings, rated 32 A.

Where can I buy the 3VA1132-4GD42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1132-4GD42-0AA0