Siemens 3VA1132-5EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-5EF32-0CA0 SENTRON MCCB, 32 A, 3-Pole, 187 k

MPN3VA1132-5EF32-0CA0

Siemens SENTRON 3VA1132-5EF32-0CA0, molded case circuit breaker, 3-pole, 32 A rated current, 187 kA breaking capacity at 240 V, line protection, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-5EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1132-5EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1132-5EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1132-5EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-5EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-5EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-5EF32-0CA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1132-5EF32-0CA0 — SENTRON MCCB, line protection, 32 A, 187 kA

3-pole molded case circuit breaker, SENTRON series, line protection, 32 A continuous current Iu, 800 V insulation voltage Ui. Breaking capacity hits 187 kA at 240 V and 121 kA at 415 V — that class of interrupting rating means it can ride through high-fault utility feeds without needing an upstream current-limiting fuse, saving panel space and coordination work. At 55 °C the rating starts to step down: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C — so an enclosure hitting 60 °C ambient still carries 30 A without nuisance tripping.

Integration & mounting

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — fits standard MCCB panel cut-outs for 160 A frame size; the IP40 front rating means it's suited for enclosed distribution boards where dust ingress is controlled. The breaker includes an undervoltage release (UVR) as the auxiliary release — wired into the safety circuit, it trips the breaker on loss of control voltage, meeting machine-guarding stop requirements without a separate shunt-trip module.

MPN