What this MCCB delivers
Its 32 A continuous rating holds across 40 °C to 50 °C ambient without derating, then tapers to 30 A at 70 °C — useful when the breaker shares a warm enclosure with other heat sources. Breaking capacity hits 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 440 V, dropping to 17 kA at 500 V and 690 V. Power dissipation is 13.1 W maximum, so panel ventilation matters if you're stacking several of these.
The 3VA1132-5EF32-0DA0 measures 130 mm high, 76.2 mm wide, 70 mm deep.