Skip to main content
Siemens 3VA1132-5EF36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-5EF36-0AG0 Circuit Breaker, 55kA @ 415V, 32A

MPN3VA1132-5EF36-0AG0

Siemens 3VA1 series, IEC frame 160, 3-pole molded case circuit breaker, breaking capacity class M (Icu=55kA @ 415V), TM240 thermal-magnetic trip unit, In=32A, overload Ir=22A...32A, short-circuit Ii=5...10 x In, clamp connection, includes 1 auxiliary switch HP and 1 trip alarm switch HP.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The TM240 thermal-magnetic trip unit gives you an adjustable overload (Ir) from 22 A to 32 A and a fixed magnetic short-circuit pickup (Ii) at 5 to 10 times In — so for a 32 A breaker, that's 160 to 320 A instantaneous. That range suits motor branch circuits or feeder protection where you need to ride through inrush without nuisance tripping.

Clamp connection terminals accept copper or aluminum conductors up to the frame's rated cross-section. The factory-fitted auxiliary switch (HP) and trip alarm switch (HP) give you remote status feedback — the auxiliary tracks the breaker's on/off position, the alarm signals a trip event. Both are wired to a terminal block on the breaker face, so you don't need to open the cover to check state.

Frequently asked questions

Where can I buy 3VA1132-5EF36-0AG0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at quote time.

What is the breaking capacity of this breaker?

The 3VA1132-5EF36-0AG0 has a rated ultimate breaking capacity (Icu) of 55 kA at 415 V AC, placing it in breaking capacity class M. This means it can safely interrupt fault currents up to 55 kA at that voltage without damage.

What trip unit does this breaker use?

It uses a TM240 thermal-magnetic trip unit. The overload protection (Ir) is adjustable from 22 A to 32 A, and the short-circuit protection (Ii) is fixed at 5 to 10 times the rated current In (32 A), so 160 to 320 A instantaneous pickup.

MPN
3VA1132-5EF36-0AG0