Skip to main content
Siemens 3VA1132-5EF36-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-5EF36-0KH0 SENTRON MCCB, 32 A, 187 kA at 240

MPN3VA1132-5EF36-0KH0

Siemens SENTRON 3VA1132-5EF36-0KH0, molded case circuit breaker, 3-pole, 32 A, 187 kA at 240 V, TM240 overcurrent release, shunt trip, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-5EF36-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1132-5EF36-0KH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1132-5EF36-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1132-5EF36-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-5EF36-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1132-5EF36-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-5EF36-0KH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB does on the line side

The Siemens SENTRON 3VA1132-5EF36-0KH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 32 A and an interrupting capacity of 187 kA at 240 V — enough to clear a high-fault utility feed without upstream coordination headaches. The TM240 thermal-magnetic overcurrent release handles the overload and short-circuit trip curves; there is no undervoltage release, no phase-failure detection, and no communication module onboard — this is a straight feeder breaker, not a smart panel device. It ships with a shunt trip (STL) auxiliary release and a 2-auxiliary-switch plus 1-trip-alarm-switch HQ contact block, so you can remote-trip it and get a separate alarm signal back to the PLC or annunciator.

Interrupting ratings — what the numbers mean for your panel

The interrupting capacity drops with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. At 415 V, that 121 kA SCCR covers most industrial distribution transformers up to 2 MVA without needing a current-limiting fuse upstream. Rated insulation voltage Ui is 800 V, so the breaker is rated for 690 V line-to-line applications — the interrupting curve above is the limiting factor, not the insulation.

Thermal derating — the real-world current you can pull

The 32 A rating holds flat from 40 °C through 50 °C ambient. Above that it derates: 30.72 A at 55 °C, 30.08 A at 60 °C, 29.44 A at 65 °C, and 28.8 A at 70 °C. If your panel internal ambient runs 60 °C, plan for 30 A continuous, not 32. Operating range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. The IP40 front protection means it is fine in a clean indoor panel but not washdown-rated.

Lifecycle and sourcing posture

The latching endurance is rated at 15 000 operations — a solid figure for a feeder breaker that cycles maybe a few times a year, but not a high-duty motor-switching device.

Physical fit and integration

Dimensions: 130 mm high, 76.2 mm wide, 70 mm deep. The 3-pole frame width of 76.2 mm is standard for this SENTRON 3VA frame size; it mounts on a DIN rail or panel-mount plate with the same footprint as other 3VA1-series breakers. The integrated auxiliary trip accessory is order code 3VA9688-0BL33 — order it alongside if you need the shunt trip wired at the factory rather than field-installed.

Frequently asked questions

What is the interrupting capacity of 3VA1132-5EF36-0KH0 at 415 V?

121 kA at 415 V, which covers most industrial distribution transformers up to about 2 MVA without requiring a current-limiting fuse upstream.

Where can I buy 3VA1132-5EF36-0KH0 and get current pricing?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does 3VA1132-5EF36-0KH0 include a shunt trip?

Yes, it is designed with a shunt trip (STL) auxiliary release and comes with 2 auxiliary switches plus 1 trip alarm switch HQ.

What is the thermal derating for 3VA1132-5EF36-0KH0 above 50 °C?

The 32 A rating holds at 40 °C through 50 °C. At 55 °C it derates to 30.72 A, at 60 °C to 30.08 A, at 65 °C to 29.44 A, and at 70 °C to 28.8 A.

MPN
3VA1132-5EF36-0KH0