Skip to main content
Siemens 3VA1132-6ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-6ED36-0AA0 SENTRON MCCB, 3-Pole, 32 A, TM210

MPN3VA1132-6ED36-0AA0
Active

Siemens SENTRON 3VA1132-6ED36-0AA0, molded case circuit breaker, 3-pole, TM210 release, 32 A, 220 kA at 240 V AC, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1132-6ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1132-6ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1132-6ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1132-6ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1132-6ED36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1132-6ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1132-6ED36-0AA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens 3VA1132-6ED36-0AA0 is a SENTRON molded case circuit breaker (MCCB) with three poles, rated 32 A continuous at 40 °C and fitted with a TM210 thermal-magnetic overcurrent release. It's designed for line protection — the primary feeder or distribution circuit in a panel, not a motor-protective function. The TM210 release means the thermal element is fixed at 32 A (no adjustable thermal dial), and the magnetic short-circuit pickup is set at 10× In (320 A). That's a standard fixed-trip curve for general distribution; you don't get the flexibility of an electronic trip, but you also don't need a separate power supply for the trip unit. Rated insulation voltage is 800 V, and the maximum operating voltage is 690 V AC or 500 V DC. The interrupting ratings are the headline: 220 kA at 240 V AC, 154 kA at 415 V AC, 121 kA at 440 V AC, and 17 kA at 500 V and 690 V AC. That 220 kA at 240 V is a high-fault-current rating — it's sized for large transformer secondaries or high-capacity busway feeds where the available fault current is well above what a standard 65 kA or 100 kA breaker can handle. At 690 V the 17 kA rating is still respectable for a 32 A frame, but if your system runs at 480 V or 600 V class, the 121 kA at 440 V gives you a good reference point for coordination studies.

Thermal derating and panel fit

The 32 A rating holds flat from 40 °C to 50 °C, then derates to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. That's a shallow derating curve — only 2 A lost over a 30 °C rise — which means the breaker runs cool and you don't have to oversize the frame for a warm enclosure. The power loss is 10.6 W maximum, so heat dissipation inside the panel is manageable even with several breakers ganged together. Physical dimensions: 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in). That's a standard 3-pole MCCB footprint for the SENTRON 3VA1 frame — it fits the same mounting hole pattern and busbar spacing as other 3VA1 breakers in the 32 A class. The front face carries an IP40 protection rating, so it's protected against tools and wires >1 mm but not sealed against dust ingress; it's intended for a closed panel, not a washdown environment.

Frequently asked questions

Where can I buy 3VA1132-6ED36-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting rating of this MCCB at 240 V?

220 kA at 240 V AC — that's a high-fault-current rating suitable for large transformer secondaries or high-capacity busway feeds.

What does the TM210 release mean?

TM210 means a fixed thermal-magnetic trip: 32 A continuous (no adjustable thermal dial) and a magnetic short-circuit pickup at 10× In (320 A). It's a standard fixed-trip curve for distribution circuits.

MPN
3VA1132-6ED36-0AA0