Skip to main content
Siemens 3VA1132-6ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-6ED36-0AA0 SENTRON MCCB, 3-Pole, 32 A, TM210

MPN3VA1132-6ED36-0AA0
Active

Siemens SENTRON 3VA1132-6ED36-0AA0, molded case circuit breaker, 3-pole, TM210 release, 32 A, 220 kA at 240 V AC, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1132-6ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1132-6ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.10.6 W
3VA1132-6ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1132-6ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-6ED36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1132-6ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-6ED36-0AA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

That's a standard fixed-trip curve for general distribution; you don't get the flexibility of an electronic trip, but you also don't need a separate power supply for the trip unit. The interrupting ratings are the headline: 220 kA at 240 V AC, 154 kA at 415 V AC, 121 kA at 440 V AC, and 17 kA at 500 V and 690 V AC. At 690 V the 17 kA rating is still respectable for a 32 A frame, but if your system runs at 480 V or 600 V class, the 121 kA at 440 V gives you a good reference point for coordination studies.

The 32 A rating holds flat from 40 °C to 50 °C, then derates to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. That's a shallow derating curve — only 2 A lost over a 30 °C rise — which means the breaker runs cool and you don't have to oversize the frame for a warm enclosure. The power loss is 10.6 W maximum, so heat dissipation inside the panel is manageable even with several breakers ganged together. Physical dimensions: 76.2 mm wide (3 in), 130 mm tall (5.12 in), 70 mm deep (2.76 in).

Frequently asked questions

Where can I buy 3VA1132-6ED36-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting rating of this MCCB at 240 V?

220 kA at 240 V AC — that's a high-fault-current rating suitable for large transformer secondaries or high-capacity busway feeds.

What does the TM210 release mean?

TM210 means a fixed thermal-magnetic trip: 32 A continuous (no adjustable thermal dial) and a magnetic short-circuit pickup at 10× In (320 A). It's a standard fixed-trip curve for distribution circuits.

MPN
3VA1132-6ED36-0AA0