The Siemens SENTRON 3VA1132-6EE36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection. It carries a 32 A continuous current at 40 °C and a massive 220 kA interrupting capacity at 240 V — that's the kind of short-circuit rating you spec for high-fault panels where a standard MCCB would weld shut. The TM220 thermal-magnetic release handles overload and short-circuit without an external trip unit.
Mounts on DIN rail or panel-mount baseplate. The 76.2 mm width (3 in) and 70 mm depth (2.76 in) fit standard 3-pole MCCB slots in most North American and European enclosures. IP40 on the front means it's fine inside a clean panel — no washdown rating, so keep it out of wet areas.
Rated insulation voltage 800 V, so it handles 480/600 V systems with headroom. The interrupting curve drops from 220 kA at 240 V to 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500/690 V — that's still a solid number for most industrial services. Operating temperature range -25 °C to 70 °C; storage from -40 °C to 80 °C. Power loss max 10.6 W.